Politically
speaking, greater attention is paid to the quantity of power delivered daily on
the national grid because it is the yardstick with which the performance of the
system is measured. This is not out of place as the public is generally
interested in the Megawatt and Energy delivered to the Discos and the Regulator
uses this quantity for settlement of claims.
Despite
this situation, Operators of the system pay attention to the quality of voltage
in the power supply delivered because most industrial and commercial machines
are set to function at certain preset values and due to poor voltage, most
organizations do not use public power supply in their operations. They prefer
to put the public power supply as an alternative source.
Generators
are expected to regulate the output voltage at their end with the help of their
exciters and additionally, power quality equipment like Reactors, Capacitor
Banks etc are installed at different Transmission stations on the grid to
correct the voltage since voltage vary from one place to the other depending on
several factors. Also, power Transformers are equipped with Tap-Changers that
are used to achieve quality power supply. Other methods adopted to correct
voltage imbalance include load management and the use of lightly loaded
transmission lines.
Poor
voltage quality can result into equipment damage, malfunction, inefficiency, and
increased costs. This has reflected in damage to terminal equipment like Capacitive
Voltage Transformers (CVT).
While
in the Nigerian grid, the statutory limits prescribed at the 330kV level is set
at 280.5 (lower limit) -346.5 (upper limit), the highest voltage recorded for
some selected days on the national grid are as follows:
HIGHEST
VOLTAGE RECORDED FOR SELECTED DAYS ON THE NIGERIAN NATIONAL GRID
S/N |
DAY |
DATE |
HIGHEST
VOLTAGE (kV) |
LOCATION
(TS) |
1 |
MONDAY |
05/02/2024 |
347 |
ONITSHA
& FAKUN |
2 |
TUESDAY |
06/02/2024 |
348 |
ONITSHA |
3 |
WEDNESDAY |
07/02/2024 |
352 |
FAKUN |
4 |
THURSDAY |
08/02/2024 |
352 |
FAKUN |
5 |
FRIDAY |
09/02/2024 |
350 |
FAKUN |
From
the above table, it is clear that the highest voltage level consistently
violated the prescribed statutory upper limit (346.5kV) and this has its
implications on the system equipment and quality of power delivered to
customers.
In
order to mitigate the adverse effect of voltage values that contradict the
statutory limits, concerned parties should focus on this variable by ensuring
that GENCOs provide the expected services required in this respect and voltage
correcting equipment are sufficiently installed at relevant locations across
the grid for the benefit of both the industry and customers.